Baseline BESS Focus Results Excess unit temperatures was dominantly due to: 1. Contamination of downstream units from upstream exhaust plumes due to the exhaust not making it far enough up into wind currents to be pulled off the site, circled on top right. 2. Local aisle re-ingestion of HVAC exhaust to their intakes because of a lack of exhaust inertia relative to intake pull, shown in slice on bottom right. Consequently, remediation solutions are a necessity for the site to be operable.