Guides

BESS Report

Issue link: https://resources.randsim.com/i/1532829

Contents of this Issue

Navigation

Page 14 of 16

45 Degree Exhaust Louver Site Thermals Remediation Solutions Comparison Minimization of local reingestion & thermal spread on the site led to a broad reduction in intake temperatures over the site. • Site contours on right show a breakdown of average HVAC intake temperatures on BESS units. • As can be seen, the 70° louver site layout overall had more green units, which is emphasized in the zoomed in section from the thermal contour at the intakes. 70 Degree Exhaust Louver Site Thermals No Exhaust Louver Site Thermals