Issue link: https://resources.randsim.com/i/1532829
Remediation Conclusion 0 50 100 150 200 250 300 350 400 45-46 46-47 47-48 48-49 49-50 50-51 51-52 52-53 53-54 54-55 55-56 56-57 57-58 58-59 Number of HVAC Units Temperature Range [C] Worst-Case Site Summary (BESS Focus) No Louvers 70° Louvers Above Threshold Baseline •Functioned at 45°C with no wind. •In presence of wind, local reingestion & thermal accumulation throttled site. •Consequentially failed requirements for performance. Modification •70° louver attached to BESS exhausts, increasing exhaust momentum. •Proved effective at mitigating both local reingestion & thermal accumulation. •Kept site below threshold limits, meeting performance standards.