Guides

BESS Report

Issue link: https://resources.randsim.com/i/1532829

Contents of this Issue

Navigation

Page 7 of 16

Baseline BESS Focus Results 0 50 100 150 200 250 300 350 400 45-46 46-47 47-48 48-49 49-50 50-51 51-52 52-53 53-54 54-55 55-56 56-57 57-58 58-59 59-60 Number of HVAC Units Temperature Range [C] Baseline Thermal Distribution Comparison No Wind 7 MPH SE 12.5 MPH SE 20 MPH SE 12.5 MPH SWW Configuration Units >54°C Threshold Median Temperature Site Energy Storage Scenario 1: No Wind 2% 49.9°C 4.8°C/unit Scenario 2: 7 MPH SE 48% 51.4°C 8.3°C/unit Scenario 3: 12.5 MPH SE 35% 52.4°C 7.3°C/unit Scenario 4: 20 MPH SE 14% 50.0°C 5.5°C/unit Scenario 5: 12.5 MPH SWW 32% 52.1°C 7.3°C/unit 7 MPH SE wind condition (Scenario 2) saw the worst performance. Units above operating temperature threshold: 918, 48% of site. Max temperature unit intakes: 58.2°C. Consequence was the site fell below a passing criteria for performance under not only the worst case, but numerous wind directions.