Issue link: https://resources.randsim.com/i/1532829
Remediation Solution Results From the analyses of the worst-case condition, it showed that both the no louver and 45° louver still had units above the threshold temperature of 54°C. In contrast, the 70° louver configuration did not exceed thresholds and maintained lower thermal energy levels across the site, shown on the chart and in the table below. Configuration Units >54°C Threshold Median Temperature Site Energy Storage No louver 48% 53.8°C 8.3°C/unit 45° louver 16% 51.4°C 6.1°C/unit 70° louver 0% 49.5°C 4.4°C/unit 0 50 100 150 200 250 300 350 400 45-46 46-47 47-48 48-49 49-50 50-51 51-52 52-53 53-54 54-55 55-56 56-57 57-58 58-59 Number of HVAC Units Temperature Range [C] Thermal Distribution Comparison at 7 MPH SE Wind No Louvers 45 ° Lover 70° Louvers Above Threshold