Guides

BESS Report

Issue link: https://resources.randsim.com/i/1532829

Contents of this Issue

Navigation

Page 9 of 16

Remediation Proposal Original Design No louvers, causing local recirculation and thermal buildup on the site. Core Issue Exhaust air needed to be ejected out of the aisles so cool fresh air could enter. Solution Proposal Implementation of 45° or 70° louvers (shown on right). Alternative Solutions •Replacing HVAC unit •Stack installation •Bolster HVAC fan Remediation Analysis •Worst-case site condition (Scenario 2: 7 MPH SE). •Compared direct to baseline configuration. 45° Exhaust Louver 70° Exhaust Louver A A Compared to louvers: •Can negatively impact maintenance schedules •May require contract modification •High manufacturing costs •Each may have installation difficulties