Baseline BESS Focus Results
Excess unit temperatures was dominantly due to:
1. Contamination of downstream units from upstream
exhaust plumes due to the exhaust not making it far
enough up into wind currents to be pulled off the site,
circled on top right.
2. Local aisle re-ingestion of HVAC exhaust to their intakes
because of a lack of exhaust inertia relative to intake
pull, shown in slice on bottom right.
Consequently, remediation solutions are a necessity for the
site to be operable.