Simulation Inputs Inverter BESS Container BESS Unit Exhaust Intake Thermal Gains Representation For BESS Units and Inverters, thermal gains are represented by a temperature gain from the intake to exhaust based on the First Law of Thermodynamics: Δ = . Maximum Operating Temperature Limitations When the maximum operating temperature of a unit is reached, it is assumed that the unit is derated to truncate dissipation to a tolerable level for the HVAC unit to handle. BESS Unit Dissipation Cycle Characteristics •Flow rate: 1236 CFM (2100 m 3 /h) •Heat rejection: 6.91 kW (10.6°C rise) •Maximum operating intake temperature of 54°C Inverter Operational Characteristics •Flow rate: 824 CFM (1400 m 3 /h) •Heat rejection: 2.54 kW (5.8°C rise) •Maximum operating intake temperature of 67°C