Case Study: Baseline Failures • Substantial deration from local reingestion & heat islanding. • To alleviate, inertia of exhausts needed to increase. • 70° louvers evaluated Configuration Units >54°C Threshold Median Temperature Site Energy Storage Scenario 1: No Wind 2% 49.9°C 4.8°C/unit Scenario 2: 7 MPH SE 48% 51.4°C 8.3°C/unit Scenario 3: 12.5 MPH SE 35% 52.4°C 7.3°C/unit Scenario 4: 20 MPH SE 14% 50.0°C 5.5°C/unit Scenario 5: 12.5 MPH SWW 32% 52.1°C 7.3°C/unit Case Study Risk Management Role of Simulation BESS & DC Overview